A 35 kV oil-immersed power transformer is selected for power conversion at the specified system voltage level. The reference catalogue provides configurations with rated capacity, winding voltages, tapping ranges, vector groups and impedance values. On-load and off-circuit tap-changing arrangements are listed separately and must be selected to suit the operating requirement. The design review should establish the required number of windings, network voltages, load profile and installation environment. Rated voltage alone is not enough to define a complete transformer specification. Buyers should also provide the frequency, required losses, insulation requirements, cooling arrangement and applicable project specification. Accessories, terminal arrangements and protection interfaces are agreed with the installation designer. For replacement projects, include the existing nameplate and foundation drawing. The catalogue tables supplied with this material package are reference data from the existing product documents. Final guaranteed values, test scope and overall dimensions must be confirmed in the project technical agreement and approved drawing before manufacture.
Oil free, with strong fire resistance, eliminating the risk of oil leakage; Capable of withstanding short-circuit current and overvoltage, and adapting to harsh environments.
Using environmentally friendly materials, low noise and no pollution, to assist in the construction of a green power grid.
Efficient cooling system ensures that the equipment maintains low temperature during long-term operation, effectively extending the service life of the equipment.
Humanized design, simple operation, convenient and fast daily inspection and maintenance, significantly reducing operating costs.
Durable shell design, impact resistance, corrosion resistance, able to adapt to various complex and harsh working environments.
Modular structure design, supporting quick disassembly and assembly, combined with intelligent monitoring system, making operation and maintenance work more worry free and effortless.
35KV oil immersed three-phase double winding non excited voltage regulating power transformer
Rated capacity (kVA) | Rated voltage and tap range | Vector group | No load current (%) | Impedance voltage (%) | No load losses (kW) | On load losses (kW) | ||
HV | Tap range(%) | LV | ||||||
3150 | 35~38.5 | ±2×2.5 | 3.15 | Yd11 | 0.36 | 7.0 | 1.7 | 20.7 |
4000 | 0.36 | 2 | 24.6 | |||||
5000 | 0.36 | 2.4 | 28.2 | |||||
6300 | 0.36 | 8.0 | 2.9 | 31.5 | ||||
8000 | ±2×2.5 | 3.15 | YNd11 | 0.28 | 4 | 34.6 | ||
10000 | 0.28 | 4.8 | 40.8 | |||||
12500 | 0.24 | 5.5 | 48.4 | |||||
16000 | 0.24 | 6.7 | 59.2 | |||||
20000 | 0.24 | 10.0 | 7.9 | 71.6 | ||||
25000 | 0.2 | 9.4 | 84.6 | |||||
31500 | 0.2 | 11.1 | 100.8 | |||||
35KV oil immersed three-phase double winding on load voltage regulating power transformer
Rated capacity (kVA) | Rated voltage and tap range | Vector group | No load current (%) | Impedance voltage (%) | No load losses (kW) | On load losses (kW) | ||
HV | Tap range (%) | LV | ||||||
3150 | 35~38.5 | ±3×2.5 | 6.3 | Yd11 | 0.4 | 7.0 | 1.8 | 22.2 |
4000 | 0.4 | 2.1 | 26.2 | |||||
5000 | 0.4 | 2.6 | 30.8 | |||||
6300 | 0.4 | 3.1 | 33 | |||||
8000 | 6.3 | YNd11 | 0.32 | 7.5或8.0 | 4.3 | 36.5 | ||
10000 | 0.32 | 5.1 | 43.2 | |||||
12500 | 0.28 | 6 | 51.1 | |||||
16000 | 0.28 | 7.2 | 63.3 | |||||
20000 | 0.28 | 8.5 | 74.4 | |||||
25000 | 0.24 | 10.0 | 10.1 | 88 | ||||
31500 | 0.24 | 12 | 104.4 | |||||
Reference diagram for external installation dimensions